HOME

SAFETY

HEALTH

ENVIRONMENT

FIRE

EMERGENCY PLAN

SECURITY

MOTOR FLEET

MAINTENANCE


PERFORMANCE 86%
AVERAGE LTIFR
0.00
TOTAL VISITS: 3,892
VIEWERS ONLINE: 77

Unit NumberLocationCoC ReportService ReportPhoto
GS2Inside Workshop GS2_COC_230426_154628.pdf VIEW REPORT VIEW
◀ July 2026 Weekly Inspections — August 2026 CURRENT MONTH Current Month
Inspection Criteria27 Jul – 02 Aug
03 Aug – 09 Aug
10 Aug – 16 Aug
17 Aug – 23 Aug
24 Aug – 30 Aug
31 Aug – 06 Sep
1. Symbolic Signage clearly visible.YesYes
2. Generator secured but easily accessible.YesYes
3. Generator started under LOAD.YesYes
4. Generator running for 1 HOUR.YesYes
5. Motor Oil level in order.YesYes
6. Diesel Fuel level above 3/4 (75%).YesYes
7. Water Coolant level in order.YesYes
8. Battery Water level in order.YesYes
9. Heating elements tested.YesYes
10. Check all connections are in good order.YesYes
11. Switches in proper positions for emergency start.YesYes
12. Generator and surroundings are clean.YesYes
13. Check all areas for emergency supply.YesYes
14. Battery Charging Voltage is correct.YesYes
15. Fuel Shut-off device fitted and tested.YesYes
16. No oil, fuel or water leaks.YesYes
17. Bund wall in place — drain valve closed.YesYes
18. Service done and up to date (OEM frequency).YesYes
19. Equipment generally in good condition.YesYes
Inspector Name
Peet schutte
Peet schutte
Date & Time
07-08-26 16:19
14-08-26 16:02