⚠️ Fault Report
Unit NumberLocationInstallation Cert.Job Card No.Photo
BP3Sprinkler Jockey Pump BP3_COC JC0379 VIEW
Showing: 13 Jul 2026 – 09 Aug 2026
Inspection Criteria ◀Wk 29Wk 30Wk 31Wk 32▶
1. Check and record pump cut-in pressure setting Yes (650 kpa)
2. Check and record pump cut-in pressure Yes (650 kpa)
3. Check and record pump cut-out pressure setting Yes (750kpa)
4. Check and record pump cut-out pressure Yes (750 kpa)
5. Check manual/auto selector switch in manual and back to auto Yes
6. Check panel indicator lamp on Yes
7. Check Pump Run signal Yes
8. Record Pump Hour Meter Reading Yes (0002649)
Name of inspector
Dean Jacobs
Date & Time of inspection
24-07-26 15:07