MAP
STATUS:
| Unit Number | Location | Installation Cert. | Job Card No. | Photo |
|---|---|---|---|---|
| BP2 | Sprinkler Booster Pump 2 - Diesel | BP2_COC | JC0379 | VIEW |
Showing: 07 Sep 2026 – 04 Oct 2026
| Inspection Criteria | ◀Wk 37 | Wk 38 | Wk 39 | Wk 40 |
|---|---|---|---|---|
| 1. Check Suction Valve open and Secured / Check Delivery Valve open and Secured |
Yes |
Yes |
||
| 2. Check Compound Gauge (Positive Pressure) |
Yes |
Yes |
||
| 3. Check engine oil levels correct |
Yes |
Yes |
||
| 4. Check Panel indicator lamp On |
Yes |
Yes |
||
| 5. Check and record cooling water gauge on the cooling line |
Yes (80) |
Yes (80) |
||
| 6. Check the cooling water sight glass clear and water flow visible |
Yes |
Yes |
||
| 7. Check engine batteries stand and mounting, engraved dates |
Yes |
Yes |
||
| 8. Record Hour Meter Reading |
Yes (1049) |
Yes (1049) |
||
| 9. Press Lamp Test Button Test |
Yes |
Yes |
||
| 10. Power Failure Alarm Test |
Yes |
Yes |
||
| 11. Check Pump Run On |
Yes |
Yes |
||
| 12. Check Pump Gland |
Yes |
Yes |
||
| 13. Record Oil Pressure reading |
Yes (450 kpa) |
Yes (450) |
||
| 14. Power Failure Alarm Test |
Yes |
Yes |
||
| 15. Record RPM reading |
Yes (2600 rpm) |
Yes (2600) |
||
| 16. Check and record Delivery Pressure |
Yes (450 kpa) |
Yes (450) |
||
| Name of inspector |
|
Dean Jacobs
|
Dean Jacobs
|
|
| Date & Time of inspection |
|
18-09-26 13:39
|
23-09-26 06:40
|
|