MAP
STATUS:
| Unit Number | Location | Installation Cert. | Job Card No. | Photo |
|---|---|---|---|---|
| BP1 | Sprinkler Booster Pump 1 - Electric | BP1_COC | JC0379 | VIEW |
Showing: 07 Sep 2026 – 04 Oct 2026
| Inspection Criteria | ◀Wk 37 | Wk 38 | Wk 39 | Wk 40 |
|---|---|---|---|---|
| 1. Check Suction Valve open and Secured / Check Delivery Valve open and Secured |
Yes |
Yes |
||
| 2. Check Compound Gauge (Positive Pressure) |
Yes |
Yes |
||
| 3. Check panel indicator lamp On |
Yes |
Yes |
||
| 4. Record Hour Meter Reading |
Yes (5970) |
Yes (5970) |
||
| 5. Press Lamp Test Button Test |
Yes |
Yes |
||
| 6. Power Failure Alarm Test |
Yes |
Yes |
||
| 7. Emergency Start Test |
Yes |
Yes |
||
| 8. Check Pump Run On |
Yes |
Yes |
||
| 9. Check and Record current drawn in Amps |
Yes (13.5) |
Yes (13.5) |
||
| 10. Check and Record Pressure on the Delivery Pipe |
Yes (470 kpa) |
Yes (450kpa) |
||
| 11. Check Pump Gland |
Yes |
Yes |
||
| 12. Test Start Button |
Yes |
Yes |
||
| Name of inspector |
|
Dean Jacobs
|
Peet Schutte
|
|
| Date & Time of inspection |
|
18-09-26 13:36
|
23-09-26 06:39
|
|