MAP
STATUS:
| Unit Number | Location | Installation Cert. | Job Card No. | Photo |
|---|---|---|---|---|
| BP1 | Sprinkler Booster Pump 1 - Electric | BP1_COC | JC0379 | VIEW |
Showing: 28 Sep 2026 – 25 Oct 2026
| Inspection Criteria | ◀Wk 40 | Wk 41 | Wk 42 | Wk 43▶ |
|---|---|---|---|---|
| 1. Check Suction Valve open and Secured / Check Delivery Valve open and Secured |
Yes |
Yes |
Yes |
|
| 2. Check Compound Gauge (Positive Pressure) |
Yes |
Yes |
Yes |
|
| 3. Check panel indicator lamp On |
Yes |
Yes |
Yes |
|
| 4. Record Hour Meter Reading |
Yes (0005998) |
Yes (0006064) |
Yes (0006070) |
|
| 5. Press Lamp Test Button Test |
Yes |
Yes |
Yes |
|
| 6. Power Failure Alarm Test |
Yes |
Yes |
Yes |
|
| 7. Emergency Start Test |
Yes |
Yes |
Yes |
|
| 8. Check Pump Run On |
Yes |
Yes |
Yes |
|
| 9. Check and Record current drawn in Amps |
Yes (13.2 amps) |
Yes (13.6 amps) |
Yes (13.4 amps) |
|
| 10. Check and Record Pressure on the Delivery Pipe |
Yes (540kpa) |
Yes (570kpa) |
Yes (520kpa) |
|
| 11. Check Pump Gland |
Yes |
Yes |
Yes |
|
| 12. Test Start Button |
Yes |
Yes |
Yes |
|
| Name of inspector |
Dean Jacobs
|
|
Dean Jacobs
|
Dean Jacobs
|
| Date & Time of inspection |
02-10-26 12:56
|
|
14-10-26 08:06
|
22-10-26 08:07
|